Improving the indoor air quality of newly-built schools with the bake-out method
ơǿ*
Abstracts
We studied the changes in the concentration of total volatile organic compounds generated in newly-built schools
(five kindergarten schools, two primary schools, three middle schools, one high school) by the bake-out. Samples
were collected in classrooms. By using the bake-out technique the removal efficiency of total volatile organic
compounds was 89.1%(maximum) and 27.5%(minimum). By using this bake-out technique the removal efficiency
was 42.5% greater than the ventilation method. Therefore, we determined that it is appropriate to apply both the
bake-out and ventilation methods in the case of newly-built schools.
Keywords : Bake-out, Indoor air quality, Newly-built school, TVOCs, Ventilation