Investigation of L. pneumopila in Water Collected from Air Conditioning Cooling Towers and Indoor Air at Different Public Facilities
漱,ڿ,,߹,
Abstracts
This study was carried out to investigate the presence of L. pneumophila in indoor air and water collected from 692 air conditioning cooling towers at different public facilities. For these 4 years(20012004) of investigation, water samples were collected in high air conditioner operating month (from July to September) at department stores, hotels, offices, hospitals, discount stores, and public agencies. It was found that L. pneumophila was present in water samples from 47 air conditioning cooling towers. The detection rate of L. pneumophila was 7.6% in 2001, 10.7% in 2002, and 9.5% in 2003, respectively. When we compared the 4 air conditioner operating months, the highest rate of L. pneumophila detection was obtained in the water samples of July. The detection rate of L. pneumophila differed among different facilities. The highest detection rate of 17.9% was found in samples from department stores. L. pneumophila was detected similarly in water samples from hospitals(8.3%) and offices(8.2%). pH, temperature, and turbidity in the 47 L. pneumophila positive water samples ranged from pH 7 to 9, from 25 to 38, and from 1.0 to 3.5, respectively.
KeywordsL. pneumophila, Indoor air, Cooling tower, Public facility